400 Series
EN - 15
3. If the measured phase-to-
earth insulation value is
lower than the set limit, the
instrument displays a screen
similar to the one reported
here to the side and gives a
long acoustic signal
AUTO
Ra = 1789
Trcd > 999ms
RP-Pe = 0.01M
Value of earth resistance
Value of the RCD’s tripping time
Value of the phase-to-earth
insulation resistance
NOT OK
30mA 50V 500V
IdN RCD UL VNom
4.
The results displayed can be saved by pressing the SAVE key twice or the
SAVE key and, subsequently, the ENTER key (§ 8.1)
5. If the instrument detects that
the phase and neutral leads
are inverted, the message
reported here to the side is
displayed. Rotate the shuko
plug or check the connection
of the single cables
AUTO
Ra = ----
Trcd = ----ms
RP-Pe = ----M
REVERSE P-N
The phase and neutral conductors
are inverted
30mA 50V 500V
IdN RCD UL VNom
6. If the instrument detects that
the phase and earth leads
are inverted, the message
reported here to the side is
displayed. check the
connection of the cables
AUTO
Ra = ----
Trcd = ----ms
RP-Pe = ----M
REVERSE P-PE
The phase and earth conductors are
inverted
30mA 50V 500V
IdN RCD UL VNom
7. If the instrument detects a
phase-to-neutral voltage and
a phase-to-earth voltage
lower than the limit, the
message reported here to
the side is displayed. Check
that the system being tested
is energized
AUTO
Ra = ----
Trcd = ----ms
RP-Pe = ----M
Low voltage
Insufficient voltage
30mA 50V 500V
IdN RCD UL VNom