GSC60
EN - 101
10. TECHNICAL SPECIFICATIONS
Accuracy is calculated as: ±[%reading + (no. of digits) * resolution] at 23°C, <80%RH.
10.1. TECHNICAL CHARACTERISTICS SAFETY SECTION
AC TRMS voltage
Range [V] Resolution [V] Accuracy
15 460
1
(3%rdg + 2digits)
Frequency
Range [Hz] Resolution [Hz] Accuracy
47.0 63.6
0.1
(0.1%reading+1digit)
Continuity of protective conductor (LOW)
Range [
] Resolution []
Accuracy (*)
0.01 9.99
0.01
(5.0reading + 3digits)
10.0 99.9
0.1
(*) after calibration of measuring cables
Test current: >200mA DC up to 2 (cables included)
Test current resolution: 1mA
Open-circuit voltage: 4 < V0 < 24V
Safety protection: error message for input voltage > approx. 10V
Insulation resistance (M)
Test voltage [V]
Range [
] Resolution []
Accuracy
50
0.01
9.99
0.01
(2.0reading + 2digits)
10.0 49.9
0.1
50.0 99.9 (5.0reading + 2digits)
100
0.01
9.99
0.01
(2.0reading + 2digits)
10.0 99.9
0.1
100.0 199.9 (5.0reading + 2digits)
250
0.01
9.99
0.01
(2.0reading + 2digits)
10.0 99.9
0.1
100 499
1
(5.0reading + 2digits)
500
0.01
9.99
0.01
(2.0reading + 2digits) 10.0 199.9
0.1
200 499
1
500 999 (5.0reading + 2digits)
1000
0.01 9.99
0.01
(2.0reading + 2digits) 10.0 199.9
0.1
200 999
1
1000 1999 (5.0reading + 2digits)
Open-circuit voltage rated test voltage -0% +10%
Rated measuring current: >1mA with 1k x Vnom (50V, 100V, 250V, 1000V), >2.2mA with 230k @ 500V
Short-circuit current <6.0mA for each test voltage
Safety protection: error message for input voltage > approx. 10V
Line/Loop impedance (Phase-Phase, Phase-Neutral, Phase-Earth)
Range [
] Resolution []
Accuracy (*)
0.01 9.99
0.01
(5%rdg + 3digits)
10.0 199.9
0.1
(*) 0.1 m in range 0.1 199.9 m (by using the optional accessory IMP57)
Maximum test current: 5.81A (at 265V); 10.10A (at 457V)
Phase-Neutral/Phase-Phase Test voltage: (100V 265V) / (173V460V); 50/60Hz ±5%
Protection types: MCB (B, C, D, K), Fuse (gG, aM)
Insulating sheath materials: PVC, Butyl rubber, EPR, XLPE