GSC60
EN - 104
Global earth resistance in systems without Neutral
Range [
] Resolution []
Accuracy
1 1999
1
-0%, +(5.0 rdg + 3)
Maximum current: < ½ I
N
set ; Ut LIM (UL): 25V or 50V
Contact voltage (measured during RCD and Ra test)
Range [V] Resolution [V] Accuracy
0 Ut LIM
0.1
-0%, +(5.0 rdg + 3V)
Contact voltage (EARTH test – TT systems)
Range [V] Resolution [V] Accuracy
0 99.9
0.1
-0%, +
(
5.0 lettura + 3V
)
Contact voltage (EARTH test – TN systems)
Range [V] Resolution [V] Accuracy
0 99.9
0.1
-0%, +
(
5.0 rd
g
+ 3V
)
100 999
1
-0%, +
(
5.0 rd
g
+ 3V
)
Earth resistance
Range [] Resolution []
Accuracy (*)
0.01 9.99
0.01
(5% reading + 3 digits)
10.0 99.9
0.1
100 999
1
1.00k 49.99k
0.01k
Test current: <10mA, 77.5Hz; Open-circuit voltage: <20Vrms
(*) If 100*Rmeas < (Rs or Rh) < 1000* Rmeas, add 5% to te accuracy. Accuracy not declared if (Rs or Rh) > 1000* Rmis
Ground resistivity
Range [M] Resolution [m]
Accuracy
0.06 9.99
0.01
(5% reading + 3 digits)
10.0 99.9
0.1
100 999
1
1.00k 9.99k
0.01k
10.0k 99.9k
0.1k
100k 999k (*)
1k
1.00M 3.14M (*)
0.01M
(*) with distance between the probes d= 10m; Distance range: 1 10m
Test current: <10mA, 77.5Hz; Open-circuit voltage: <20Vrms
Phase rotation with 1 test lead
Voltage range P-N, P-PE[V] Frequency range
100 265 50Hz/60Hz 5%
Measurement is only carried out by direct contact with metal live parts (not on insulation sheath).
Voltage drop
Range [%] Resolution [%] Accuracy
0 100
0.1
(
10%rd
g
+ 4d
g
t
)
Voltage range Phase-Earth, Phase-Neutral: 100 265V, Frequency: 50/60Hz 5%
Leakage current (input I1 – STD clamp)
FS AC Clamp [A] Resolution [A] Accuracy
1 0.1mA
(1rdg + 20dgt)
1< FS < 10 0.01A
10 FS < 300
0.1A
300 FS 3000
1A