GSC60
EN - 103
Test on RCD without integral current breaking device (with accessory RCDX10)
Differential protection type (RCD): AC ( ), A ( ), B( ) – Generali (G), Selettivi (S) e Ritardati ( )
Voltage range Phase-Earth, Phase-Neutral: 100V 265V RCD type AC and A, 190V 265V RCD type B
Rated tripping currents (IN): 0.3A 10A
Frequency: 50/60Hz 5%
RCD without integral current breaking device tripping current - (for General RCD only)
RCD type
I
N Range I
N
[mA]
Resolution [mA] Accuracy
AC, A
300mA <IN 6.5A
(0.3 1.1) I
N
0.1I
N
- 0%, +5%I
N
B
300mA IN 1A
Duration of RCD without integral current breaking device tripping time – TT/TN systems
x 1/2 x 1 x 2 x 5 AUTO
\ G S
G S
G S
G S
G S
G S
0.3A
1.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999 310
1.1A
3.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999
3.1A
6.5A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999
6.6A
10.0A
AC 999 999 999 999 999 999 200 250
A 999 999 999 999 999 999
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:(2.0reading + 2digits)
Duration of RCD without integral current breaking device tripping time – IT systems
x 1/2 x 1 x 2 x 5 AUTO
\ G S
G S
G S
G S
G S
G S
0.3A
3.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A
B
3.1A
6.5A
AC 999 999 999 999 999 999 200 250 50 150
310
A
B
6.6A
10.0A
AC 999 999 999 999 999 999 200 250
A
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:(2.0reading + 2digits)
Overall earth resistance without RCD tripping (Ra)
Voltage range Phase-Earth, Phase-Neutral: 100 265V, Frequency: 50/60Hz 5%
Global earth resistance in systems with Neutral
Range [
] Resolution []
Accuracy
0.01 9.99
0.01
(5 reading + 0.1)
10.0 199.9
0.1
(5 reading + 1)
200 1999
1
(5 reading + 3)
Ut LIM (UL): 25V or 50V, Maximum current: <15mA