48
Felkoder i kontrollpanel
Frekvensomriktare: Felkod 0 - 14
Felkod: Visas i display: Förklaring:
0 No fault
1 Reserved
2 [Control EEprom]
(EEF1)
Internal memory fault, control card.
3 [Incorrect cong]
(CFF)
Option card changed or removed. Control card replaced by a control card congured on a
drive with a different rating. The current conguration is inconsistent.
4 [Invalid cong]
(CFI)
Invalid conguration. The conguration loaded in the drive via the bus or communication
network is inconsistent.
5 [Modbus com.]
(SLF1)
Interruption in communication on the Modbus bus.
6 [internal com. link]
(ILF)
Communication fault between option card and drive.
7 [Com. network]
(CnF)
Communication fault on communication card.
8 [External t-LI/Bit]
(EPF1)
Fault triggered by an external device, depending on user.
9 [Overcurrent]
(OCF)
Parameters in the [SETTINGS] (SEt-) and [1.4 MOTOR CONTROL] (drC-) menus are not
correct. Inertia or load too high. Mechanical locking.
10 [Precharge]
(CrF1)
Pre-charge relay control fault or charging resistor damaged.
11 [Speed fdback loss]
(SPF)
Encoder feedback signal missing.
12 [Load slipping]
(AnF)
The encoder speed feedback does not match the reference.
13 [AI2 4-20 mA loss]
(LFF2)
Loss of the 4-20 mA reference on analog input AI2.
14 [PTC1 probe]
(PtF1)
PTC1 probes open or short-circuited.