A Preventive Maintenance Table
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
147
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
N/A
Check that the
electrical
components,
control
components, SPDs,
and voltage
detection boards of
the outdoor unit are
free from dirt.
components,
control
components, and
voltage detection
boards.
N/A
Check that the
surfaces of the
control board,
SPDs, and voltage
detection boards
are not aged.
Replace the
abnormal board.
N/A
Check that the
electric heater
contactor works
properly.
1. When the air
conditioner is
on, on the
Controls page,
choose
Diagnostic
Mode > Input,
and click
Submit.
2. Choose
Running
Parameters >
Diagnostic
Mode Para, set
Elec heater
manual control
to On, and click
Submit. You
can hear a click
sound from the
contactor.
Replace the
electric heater
contactor if it is
faulty.
Cable
N/A
Check that no
cable is aged.
Replace aged
cables.
Outdoor unit
N/A
Check that the
outdoor unit is
secured to the
floor.
Tighten the screw
that secures the
rack to the floor.

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals