Ambient Temperature
()
Pressure (Bar) of
227M38UFAA
Pressure (Bar) of
SPS020-MS-032B-EN
25 26.2 26.54
30 27.4 28.46
35 28.6 30.38
40 29.8 32.31
45 31.0 34.23
50 32.2 36.15
Note: The actual cylinder pressure should not be lower than 90% of the
specied pressure at the corresponding ambient temperature.
Step 8 Install the re cylinder.
Step 9 Remove the safety cap of the release vent.
Step 10 (Optional) Install the changeable-diameter joint to the release vent using a torque
wrench.
Step 11 Wrap eight turns of sealing tape around the external threads of the changeable-
diameter joint, and install the high-pressure elbow to the changeable-diameter
joint using a torque wrench.
Step 12 Wrap eight turns of sealing tape around the external thread connector of the
extinguishant release hose and install the extinguishant release hose to the high-
pressure elbow using a torque wrench.
NO TE
Remove any old sealing tape from the threads.
If there is no changeable-diameter joint, install the high-pressure elbow directly to the
re cylinder.
Step 13 Place the white gasket in the nut end of the extinguishant release hose and install
the hose active connector to the ESS piping using a torque wrench.
LUNA2000-2.0MWH Series Smart String ESS
User Manual 4 Installation
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 108