C Crimping an OT or DT Terminal
Requirements for OT/DT Terminals
If a copper cable is used, use copper wiring terminals.
If a copper-clad aluminum cable is used, use copper wiring terminals.
If an aluminum alloy cable is used, use copper-to-aluminum wiring terminals,
or aluminum wiring terminals with copper-to-aluminum washers.
NO TICE
Do not connect aluminum wiring terminals to the terminal block. Otherwise
electrochemical corrosion may occur,
aecting the reliability of cable
connections.
Comply with the IEC 61238-1 requirements when using copper-to-aluminum
wiring terminals, or aluminum wiring terminals with copper-to-aluminum
washers.
Ensure that the aluminum side of the washer contacts the aluminum wiring
terminal, and the copper side contacts the terminal block.
LUNA2000-2.0MWH Series Smart String ESS
User Manual C Crimping an OT or DT Terminal
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 243