Step 3 Observe the progress bar and wait until the log export is complete.
Step 4 After the export is successful, click Log archiving to save the logs.
----End
A.2.4 Checking Alarms
Step 1 Choose Overview > Active Alarm.
Figure A-8 Checking alarms
----End
A.2.5 Clearing Alarms
You can clear all active and historical alarms for the selected device and re-collect
alarm data.
Procedure
Step 1 Choose Maintenance > Device Mgmt. > Clear Alarm.
Figure A-9 Clearing alarms
Step 2 Select the name of the device whose alarms are to be cleared, click Submit, and
choose All, Locally synchronized alarms, or Alarms stored on devices to clear
alarms.
----End
If alarms are cleared for the CMU, you must reset alarms on the management system.
Otherwise, the SmartLogger cannot obtain the alarm information collected by the CMU
after the alarms are cleared.
LUNA2000-2.0MWH Series Smart String ESS
User Manual A Operations on the CMU WebUI
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 238