Procedure
Step 1 Choose Maintenance > Connect Device on the SmartLogger WebUI.
Step 2 Click in the upper right corner to start devices in batches.
Figure 8-15 System startup
----End
8.4 Check Alarms
Step 1 Log in to the SmartLogger WebUI and check whether an alarm is generated. If no
alarm is generated, proceed with the power-on operations. If an alarm is
generated, clear the alarm by referring to the handling suggestions.
Step 2 Short-circuit the water sensor and check whether a water alarm is generated on
the SmartLogger WebUI:
If a water alarm is generated, the water sensor is properly connected. In this
case, the water alarm will be cleared after the short circuit is removed.
If no water alarm is generated, check whether the water sensor cable is
properly connected.
Figure 8-16 Position of Electrode Water Sensor in Battery Cabin
LUNA2000-2.0MWH Series Smart String ESS
User Manual 8 SmartLogger Web-based Deployment
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 169