EasyManua.ls Logo

Huawei LUNA2000-2.0MWH Series - Input;Output Modules

Huawei LUNA2000-2.0MWH Series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical
Specications
Fire Cylinder
Operating
voltage
24 V DC 24 V DC 24 V DC
Storage
pressure (at
20°C)
2.5 Mpa 2.5 Mpa 2.5 Mpa
Maximum
operating
pressure (at
50°C)
4.2 Mpa 4.2 Mpa 4.2 Mpa
Startup mode Electromagne
tic startup
Electromagnetic
startup
Electromagnetic startup
Electromagnetic
startup voltage/
current
24 V DC/0.6 A 24 V DC/0.6 A 24 V DC/1 A
Operating
temperature
-10°C to
+55°C
-10°C to +60°C 0 to 50
Relative
humidity
≤ 95% RH
(non-
condensing at
40°C)
≤ 95% RH (non-
condensing at
40°C)
≤ 95% RH (non-
condensing)
Outer diameter
of cylinder
≤ 324 mm 324 mm 328 mm
Cylinder height ≤ 706 mm 730 mm 918 mm
Gas release
time
6s to 10s ≤ 10s ≤ 10s
Hose Length: 800
mm;
diameter:
DN20
Length: 800 mm;
diameter: DN30
Length: 800 mm;
diameter: DN20
Extinguishing
Chemical
HFC-227ea HFC-227ea HFC-227ea
Nominal
Capacity
38 L 32 L 40 L
2.6.4.6 Input/Output Modules
NO TE
Only some models are equipped with input/output modules.
LUNA2000-2.0MWH Series Smart String ESS
User Manual 2 Overview
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 66