Alarm
ID
Alarm
Name
Severity Possible Cause Suggestion
3029 Battery
Pack
Locked
Major Cause ID = 1, 2
The battery pack has
triggered the same
fault for multiple times.
1. Determine the positions of the
input and output circuit breakers
of the ESC corresponding to
[ESR-CabinetNo ESM-SlotNo].
2. Issue a shutdown command,
turn
o the switch on the
battery side, the switch on the
bus side, and the AC power
supply switch, and wait for 24
hours.
3. Turn on the AC power supply
switch, the switch on the battery
side, and the switch on the bus
side in sequence, and issue a
startup command.
4. If the alarm persists, contact
your dealer or technical support.
Cause ID = 3–5
The battery pack has
triggered the same
fault for multiple times.
1. Determine the positions of the
input and output circuit breakers
of the ESC corresponding to
[ESR-CabinetNo ESM-SlotNo].
2. Issue a shutdown command,
turn
o the switch on the
battery side, the switch on the
bus side, and the AC power
supply switch, and wait for 5
minutes.
3. Turn on the AC power supply
switch, the switch on the battery
side, and the switch on the bus
side in sequence, and issue a
startup command.
4. If the alarm persists, contact
your dealer or technical support.
LUNA2000-2.0MWH Series Smart String ESS
User Manual 10 Alarm Reference
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 209