1. Slide the system subrack into the cabinet along guide rails.
2. Use M6 screws to x the system subrack in the cabinet.
3. Ensure that the system subrack is horizontally installed and tightly screwed.
Figure 7-38 Installing a system subrack
Step 9 Connect cables to the system subrack and press the Power button to power on the
storage device.
Step 10 When the Power indicator is steady on, check whether each component is in
normal state.
● If yes, the system subrack has been successfully installed.
● If no, cables are incorrectly connected, components are incorrectly installed, or
the newly installed system subrack is faulty.
Step 11
Conrm the replacement.
1. Perform a post-replacement inspection.
After the parts replacement, return to the SmartKit page and click Replaced.
Then complete the parts check after the replacement as prompted.
2. Check system status.
On the Parts Replacement page, click Inspection to check the system status
again. If any item fails inspection, rectify the fault based on the suggestions in
the inspection report.
3. After the preceding procedure is complete, check services on the host for
storage-related errors.
----End
OceanStor V5 Series
Parts Replacement 7 Replacing FRUs
Issue 15 (2019-12-30) Copyright © Huawei Technologies Co., Ltd. 173