No. Symptom Possible Cause Measure
The UPS is
overloaded.
Shut down all loads, and
restart the UPS.
5 The mains indicator is
o.
The mains
voltage or
frequency
exceeds the
UPS input
range.
Use a multimeter to verify that
the input voltage and
frequency meet specications.
6 The battery discharge
time is obviously
shorter than the
standard time.
Batteries are
not fully
charged.
Charge batteries for more than
8 hours when the mains is
normal. Test the discharge
time again.
The battery
performance
deteriorates.
Contact local technical support
to replace batteries.
7 Abnormal noise or
smell is generated in
the UPS cabinet.
The UPS is
faulty.
Shut down the UPS and cut o
the power input immediately.
Contact local technical
support.
8 The battery indicator
blinks. The buzzer
buzzes for 1 second
and then stops for 1
second. The battery
reserve is
insucient.
The UPS is about to
shut down.
The UPS will
soon shut
down due
to
insucient
battery
reserve, and
loads will be
powered
o.
The number
of batteries
and battery
capacity are
incorrectly
set.
Save load data immediately
and shut down primary
loads to avoid data loss or
damage.
Connect the UPS input to
the backup AC power
supply immediately.
Verify that the number of
batteries and battery
capacity are correctly set
based on the actual
conguration.
9 The user forgot the
password.
- If the user forgot only the
LCD password (the preset
password is 000001), use
the feature code (the preset
feature code is 999999) to
activate the LCD password.
If the user forgot the LCD
password and feature code,
contact local technical
support.
UPS2000-G-(6 kVA-20 kVA)
User Manual 8 Troubleshooting