G Battery Shallow Discharge Test
Context
A shallow discharge test method that tests the battery loop reliability and short-
time backup capacity after batteries are charged for a long time (60 days by
default, 30 days to 90 days
congurable).
NO TICE
Before a shallow discharge test, ensure that the load rate is 0%–100% and the
load uctuation does not exceed 10%.
Procedure
Step 1 Check the battery status for test start conditions.
1. On the Main Menu screen, choose Status and press
. On the Status
screen, locate Battery Status.
Figure G-1 Battery Status screen
UPS2000-G-(6 kVA-20 kVA)
User Manual G Battery Shallow Discharge Test
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 158

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C

Related product manuals