Item 6 kVA 10 kVA 15 kVA 20 kVA
Humidity 0%–95% RH (non-condensing)
Altitude < 1000 meters
When the altitude ranges from 1000 m to 4000 m, the
output power is derated by 1% for each additional 100 m.
Storage and
transportation
temperature
–40ºC to +70ºC
● The ESS-240V12-7AhBPVBA01/ESS-240V12-7AhBPVBA02/ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA02 battery packs can be stored and transported at a temperature
ranging from –20°C to +40°C.
● The ESS-240V12-7AhBPVBA04/ESS-240V12-9AhBPVBA04 battery packs can be stored
and transported at a temperature ranging from –15°C to +50°C.
9.3 Mains Input Electrical Specications
● For UPS2000-G-6 kVA and UPS2000-G-10 kVA, if the UPS input uses two live
wires (208 V/220 V system), all L and N wires change to L1 and L2 wires. If the
AC input of the UPS2000-G-10 kVA uses two live wires, connect AC INPUT L1,
L2, and L3 that are short-circuited with a short-circuit busbar to live wire L1,
and connect AC INPUT N to live wire L2.
● If the AC input of the UPS2000-G-15 kVA/20 kVA uses two live wires, connect
bypass and mains input bL1, bL2, bL3, mL1, mL2, and mL3 that are short-
circuited with a short-circuit busbar to live wire L1, and connect the input N
and N with a short-circuit busbar to live wire L2.
● In addition, if the AC input and AC output uses two live wires, the input and
output ends must connect to two-pole circuit breakers provided by the user.
Table 9-4 6 kVA/10 kVA mains input electrical specications
Item
6 kVA 10 kVA
Input power
cable
Single-phase (L/N) input +
PE cable
● Single-phase (L/N) input +
PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
UPS2000-G-(6 kVA-20 kVA)
User Manual 9 Technical Specications
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 123