Item 6 kVA 10 kVA
Rated input
voltage
220 V AC/230 V AC/240 V
AC
● 220 V AC, 230 V AC, or 240
V AC (single-phase input)
● 380 V AC, 400 V AC, or 415
V AC (three-phase input)
Input voltage 80–280 V AC (When the
voltage is 80–176 V AC, the
load power is linearly
derated to 40%–100%.)
● 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to 40%–
100%.)
● 138–485 V AC, three-phase
(When the voltage is 138–
305 V AC, the load power
is linearly derated to 40%–
100%.)
Input power
factor (100%
resistive load)
> 0.99 ● > 0.99 (single-phase input)
● > 0.95 (three-phase input)
No-load loss < 54 W < 90 W
Double-power
input
Disabled Disabled
Startup voltage 120–280 V AC
Diesel generator
input capacity
Minimum 1.5 times the UPS rated capacity
Table 9-5 15 kVA/20 kVA mains input electrical specications
Item
15 kVA 20 kVA
Input power
cable
● Single-phase (L/N) input +
PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
● Single-phase (L/N) input
+ PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
Rated input
voltage
● 208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase input)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
input)
● 208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase input)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
input)
UPS2000-G-(6 kVA-20 kVA)
User Manual 9 Technical Specications