F Alarm Handing of Battery Maintenance
Notication
Context
If no battery shallow discharge test is performed within 60 days after a UPS2000-
G is installed and the maintenance notication time has arrived, the mains
indicator is on, the battery and bypass indicators are
o, the fault indicator on the
INFO button is blinking red, and alarms are generated intermittently.
Procedure
Step 1 Clear the Batt. maint. notif alarm.
1. Press the i button on the UPS control panel to display the Active Alarms
page. If multiple active alarms exist, use the ▲ or ▼ button to select the
alarm record on the top (the latest alarm is on the top by default). Press
to view the alarm ID and name.
Figure F-1 Viewing alarms
2. Press to display the Maintain Batteries screen. Then the Batt. maint.
notif alarm disappears and timing for the next notication starts, regardless
of whether you perform a discharge test. The battery maintenance
notication 0036-01 in the active alarm menu will disappear.
UPS2000-G-(6 kVA-20 kVA)
User Manual
F Alarm Handing of Battery Maintenance
Notication
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 156

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C

Related product manuals