F Alarm Handing of Battery Maintenance
Notication
Context
If no battery shallow discharge test is performed within 60 days after a UPS2000-
G is installed and the maintenance notication time has arrived, the mains
indicator is on, the battery and bypass indicators are
o, the fault indicator on the
INFO button is blinking red, and alarms are generated intermittently.
Procedure
Step 1 Clear the Batt. maint. notif alarm.
1. Press the i button on the UPS control panel to display the Active Alarms
page. If multiple active alarms exist, use the ▲ or ▼ button to select the
alarm record on the top (the latest alarm is on the top by default). Press
to view the alarm ID and name.
Figure F-1 Viewing alarms
2. Press to display the Maintain Batteries screen. Then the Batt. maint.
notif alarm disappears and timing for the next notication starts, regardless
of whether you perform a discharge test. The battery maintenance
notication 0036-01 in the active alarm menu will disappear.
UPS2000-G-(6 kVA-20 kVA)
User Manual
F Alarm Handing of Battery Maintenance
Notication
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 156