Table 4-36 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item Description Default Value Value Range
Test
noticati
on
Determine whether to
periodically send shallow
discharge test notications.
The values include Disabled
and Enabled. The default
value is Disabled. If the
value is Enabled, the
system sends shallow
discharge test
notications.
The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Time
interval
Set the time interval for
shallow discharge tests. The
parameter is congurable in
any mode.
60 days 30–90 days
Discharge
ratio
Set the proportion of the
discharge capacity to the
total discharge capacity. The
parameter is congurable in
any mode.
20% 10%–50%
4.6.3.5 Restoring Factory Settings
You can restore factory settings after the inverter shuts down.
4.6.4 Control
On the Main Menu screen, select Control, and press
. The Control screen is
displayed.
Startup
The Startup menu allows you to start the inverter.
Figure 4-44 Startup screen
Shutdown
The Shutdown menu allows you to shut down the inverter.
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 91