NO TICE
For UPS2000-G-6 kVA and UPS2000-G-10 kVA, if the UPS input uses two live
wires (208 V/220 V system), all L and N wires change to L1 and L2 wires.
If the AC input of the UPS2000-G-10 kVA uses two live wires, connect AC
INPUT L1, L2, and L3 that are short-circuited with a short-circuit busbar to live
wire L1, and connect AC INPUT N to live wire L2.
If the AC input of the UPS2000-G-15 kVA/20 kVA uses two live wires, connect
bypass and mains input bL1, bL2, bL3, mL1, mL2, and mL3 that are short-
circuited with a short-circuit busbar to live wire L1, and connect the input N
and N with a short-circuit busbar to live wire L2.
In addition, if the AC input and AC output use two live wires, the input and
output ends must connect to two-pole circuit breakers provided by the user.
UPS2000-G-(6 kVA-20 kVA)
User Manual 2 Quick Introduction
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 21

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C