Item Description Default
Value
Value
Range
Auto
check
bus
capa.
Species whether to automatically
check the bus capacitance upon power-
on and generate capacitance failure
warnings. If the value is set to Enabled,
the UPS startup time takes additional
30 seconds to 180 seconds. This
parameter is
congurable only after
the inverter is shut down.
Note: This parameter is
congurable
only for the 15 kVA/20 kVA UPS.
Enabled Disabl
ed,
Enable
d
Auto
start
Species whether to automatically start
normal mode after the UPS connects to
the mains. This parameter is
congurable only after the inverter is
shut down.
Disabled Disabl
ed,
Enable
d
No
battery
alarm
If this parameter is set to Disable, the
No battery alarm is not reported. This
parameter automatically changes to
Enable after batteries are connected.
This parameter is congurable only
when batteries are not connected.
NOTE
If batteries are connected and you try to set
this parameter, the system displays a
message indicating that batteries are
connected and this parameter cannot be set.
Enabled Disabl
ed,
Enable
d
EPO
enable
Species whether to enable EPO. EPO is
performed only when this parameter is
set to Enable and the EPO switch is
triggered. This parameter is
congurable only for the UPS2000-
G-15KRTL-01/UPS2000-G-20KRTL-01.
Disabled Disabl
ed,
Enable
d
4.6.3.4 Battery Parameters Screen
CA UTION
The congured number of batteries on the LCD must match the actual number.
When the actual number changes, update the congured number. If the
congured number is less than the actual number, the battery lifespan is
shortened. If the congured number is greater than the actual number, battery
leakage may cause a
re.
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 78

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C