Item Description Default
Value
Value
Range
Auto
check
bus
capa.
Species whether to automatically
check the bus capacitance upon power-
on and generate capacitance failure
warnings. If the value is set to Enabled,
the UPS startup time takes additional
30 seconds to 180 seconds. This
parameter is
congurable only after
the inverter is shut down.
Note: This parameter is
congurable
only for the 15 kVA/20 kVA UPS.
Enabled Disabl
ed,
Enable
d
Auto
start
Species whether to automatically start
normal mode after the UPS connects to
the mains. This parameter is
congurable only after the inverter is
shut down.
Disabled Disabl
ed,
Enable
d
No
battery
alarm
If this parameter is set to Disable, the
No battery alarm is not reported. This
parameter automatically changes to
Enable after batteries are connected.
This parameter is congurable only
when batteries are not connected.
NOTE
If batteries are connected and you try to set
this parameter, the system displays a
message indicating that batteries are
connected and this parameter cannot be set.
Enabled Disabl
ed,
Enable
d
EPO
enable
Species whether to enable EPO. EPO is
performed only when this parameter is
set to Enable and the EPO switch is
triggered. This parameter is
congurable only for the UPS2000-
G-15KRTL-01/UPS2000-G-20KRTL-01.
Disabled Disabl
ed,
Enable
d
4.6.3.4 Battery Parameters Screen
The congured number of batteries on the LCD must match the actual number.
When the actual number changes, update the congured number. If the
congured number is less than the actual number, the battery lifespan is
shortened. If the congured number is greater than the actual number, battery
leakage may cause a
re.
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 78