Table 9-10 Backup time parameters for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (10 kVA, calculated based on 94% battery
eciency)
Load (%) Load (W) One
Battery
Pack
(min)
Two
Battery
Packs
(min)
Three
Battery
Packs
(min)
Four
Battery
Packs
(min)
100% 9000 4 12 23 32
80% 7200 7 17 29 44
50% 4500 12 32 53 70
30% 2700 26 57 88 125
 
Figure 9-2 Backup time curve for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (10 kVA, calculated based on 94% battery
eciency)
UPS2000-G-(6 kVA-20 kVA)
User Manual 9 Technical Specications