Huawei UPS2000-G Series - Alarm Handling of Battery Maintenance Notification

Huawei UPS2000-G Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Charge curr.
limit (UPS2000-
G-15KRTL-01/
UPS2000-
G-20KRTL-01)
1.0–2.0 A
(standard
model)
1.0–4.0 A (long
backup time
model)
2.0 A
Overcurrent
thres.
(congurable
only for the
UPS2000-G-15
kVA/20 kVA)
2.0–4.0 A
(standard
model)
4.0–8.0 A (long
backup time
model)
3.0 A
(standard
model)
6.0 A (long
backup time
model)
Battery string
sharing
Enabled and
Disabled
Disabled
Equalized
Charge
Equalized
charging
Enabled and
Disabled
Enabled
Time interval 30–180 days 60 days
Voltage 2.33–2.40 V/cell 2.35 V/cell
Max. current
(UPS2000-
G-6KRTS/
UPS2000-
G-10KRTS/
UPS2000-
G-15KRTL/
UPS2000-
G-20KRTL)
1.0–2.0 A
(standard model)
1.0–4.0 A (long
backup time
model)
2.0 A
Max. time 600–999 minutes 960 min
Float Charge Voltage 2.25–2.30 V/cell 2.25 V/cell
Temp. comp.
coef.
0.0–6.0 mV/
(°C*cell)
3.3 mV/(°C*cell)
Discharge Max. time
(congurable in
non-battery
mode)
0–24 hours 16 hours
EOD mode
(congurable in
non-battery
mode)
Batt. protect rst,
Backup time rst,
and Balanced
mode
Backup time rst
UPS2000-G-(6 kVA-20 kVA)
User Manual D LCD Menus and Parameters
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 148