Table 4. System maximum measured power specications
Product kVA Amps Power Supplies Inlet Watts
4U IBM Storage Scale
System 6000 (MTM
5149-F48), 48-drives
conguration
4.50 22.50
4 C20 4800
*
*Note: This value represents the absolute maximum power draw of the power supplies.
Actual power consumption will vary relative to workload/system utilization. For example,
for a fully populated IBM Storage Scale System 6000 (48 NVMe drives) at a theoretical
100% system utilization, the estimated power consumption is ~3.2kW.
To aid in power and cooling requirements planning, the following table lists the rating of each power
module by enclosure.
The power that is used by the system depends on various factors, including the number of enclosures and
drives in the system and the ambient temperature.
Table 5. Power rating specications per power module
Model and type PSU
Input power
requirements
Maximum input
current
Maximum power
output
4U IBM Storage Scale
System 6000 (MTM
5149-F48), 48-drives
conguration
2400 W (4)
200 V to 240 V
single phase AC
At a frequency of
50 Hz or 60 Hz
IEC C20
standardized
13A (x4) 2400 W
Note: The data in Table 4 on page 24 and Table 5 on page 24 measurements are presented as an
example. Measurements that are obtained in other operating environments might vary. Conduct your own
testing to determine specic measurements for your environment.
Each IBM Storage Scale System 6000 enclosure contains two power modules for redundancy. The
total power consumption values represent the total power that is drawn by both power modules when
operating together or a single power module when operating in a maintenance or failure mode.
Environmental requirements
System airflow is from the front to the rear of each enclosure:
Airflow passes between drive carriers and through each enclosure.
The combined power and cooling module exhausts air from the rear of each canister.
Ensure that your environment falls within the ranges that are listed in the following table.
Table 6. Temperature requirements
Environment Ambient temperature Altitude Relative humidity
Operating
5°C to 35°C
1
(41°F to 95°F)
-61 to 3048 m
2, 3
(-200 to 10000 ft)
20% to 80%
noncondensing
Nonoperating
5°C to 45°C
(41°F to 113°F)
10% to 90%
noncondensing
Transit
-40°C to 60°C
(-40°F to 140°F)
-61 to 12192 m
(-200 to 40000 ft)
10% to 90%
noncondensing
24IBM Storage Scale System 6000: Hardware Planning and Installation Guide