EasyManuals Logo
Home>INIM Electronics>Control Panel>SmartLoop

INIM Electronics SmartLoop Installation Manual

INIM Electronics SmartLoop
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Installation Manual
Troubleshooting 49
9.5 SmartLoopNET Fault
(error in the token ring network configuration)
Figure 45 - Access Denied message
This message appears when:
The SmartLoopNET board is not operating properly.
- Check that the board is inserted properly.
- Relaunch the auto-configuration phase.
- Ensure that the blue LED [Danger:3] stays On while this phase is running, and that the NODE A
[Danger:5] and NODE B [Danger:4] activity LEDs blink briefly to indicate communication attempts
on both branches.
If no LEDs go On (including the IN-NET LED), the board may be damaged and might need
replacing.
Duplicated address (address assigned to more than one control panel)
- Access the
Main menu from the panel.
- Select
Programming>Configuration>View Configuration>NET
(Programming>Configuration>View Configuration>NET).
- Check the address of each panel in the token-ring network and rectify the error.
Network Loop open
The token-ring network cabling must be closed properly otherwise the system will be unable to
configure properly.
Check the integrity of the ring cabling, as follows:
- Restore all the panels in the token-ring network to address O.
- Remove the network terminal boards [Danger:2 and 6] from the SmartLoopNET board of one of
the panels and check the continuity of wiring in the D+ circuit (between D+ poles of ports A and
B), D-circuit (between D- poles of ports A and B) and the two GND.
9.6 NET Link ALARM-A
Wiring fault in the emergency alarm ring circuit.
Check the integrity of the circuit wiring of the panel that generated the event.
- Using a multimeter or similar tool, measure the voltage over ALARM-A “+” and “-” terminals.
Under normal operating conditions the value should be approximately 2.5 V.
If the value is nearer to 5 V, the connection with terminals ALARM-B “+” and “-” of the adjacent
control panel is interrupted.
- Check the integrity of the connection.
If the voltage is nearer to 0 V, there may be a short-circuit between the two poles that connect the
ALARM-A “+” and -” terminals of the board concerned with the ALARM-B “+” and “-” terminals of
the antecedent board.
Note: If the emergency alarm loop is not used, it must be disabled via software, otherwise it will signal
a persistent fault condition.
Access to Network Denied

Table of Contents

Other manuals for INIM Electronics SmartLoop

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics SmartLoop and is the answer not in the manual?

INIM Electronics SmartLoop Specifications

General IconGeneral
BrandINIM Electronics
ModelSmartLoop
CategoryControl Panel
LanguageEnglish

Related product manuals