Installation Manual
Argus devices supported by the control panel 51
Appendix B
Argus devices supported by the control panel
Note: The ARGUS devices accepted by this control panel do not have IMQ-SISTEMI DI SICUREZZA
certification, refer to the instructions leaflet provided with each device.
All Argus Vega devices have built-in loop isolators. Therefore, isolators are not required. A short-
circuit on the loop will not provoke loss of any device.
Each detector is equipped with a 3-colour LED: green (periodic blinking) indicates the detector is
working properly (if enabled). Yellow indicates that the detector is not operating properly (fault) or
has an open isolator, whereas red indicates alarm status.
Detectors are equipped with test LEDs: if you hold a magnet near the detector base (near to the two
notches) the detector should generate an alarm signal.
B.1 Devices
B.2 Device Bases
Model Name Description Note
V100 Analogue Photo detector Optical Smoke detector
V200 Analogue Multicriteria detector Optical Smoke/Heat detector
V350 Analogue heat detector Heat detector
(
a
)
a. Configured as “Rate-of-rise detector” at default (alarm is triggered by rapid rise in temperature or when the tempera-
ture exceeds the 54°C alarm threshold).
To configure as “High temperature detector” ( Rate-of-rise feature bypas-
sed and fixed temperature set at 70°C)
use the VPU100 programmer. The panel will recognize the configuration
criteria automatically.
VMI100 Input Module Module with 1 Supervised Input
VMMI100 Input Mini Module Mini module with 1 Supervised Input
(
b
)
b. Smaller model for customized housing.
VMC100 Output Module Module with 1 Supervised Output
VMMC100 Output Mini Module Mini Module with 1 Supervised Output
(
b
)
VMC120 Output Module Form C Module with 1 form C Output (1 NON-Supervised Output)
VMMC120 Output Mini Module Form C Mini Module with 1firm C Output (1 NON-Supervised
Output)
(
b
)
VMIC100 Input Output Module Module with 1 Supervised Input + 1 Supervised Output
VMMIC100 Input Output Mini Module Mini Module with 1 Supervised Input + 1 Supervised
Output
(
b
)
VMIC120 Input output Module Form C Module with 1 Supervised Input + 1 NON-Supervised
Output (dry contact)
VMMIC120 Input output mini Module Form C Mini Module with 1 Supervised Input + 1 NON-Supervised
Output (dry contact)
(
b
)
VLS100 Intelligent Wall Sounder Loop Powered Sounder
Model Name Description Note
VB100 Vega Universal Base Standard Base x Detectors