52 Argus devices supported by the control panel
B.3 Wireless devices
B.4 Device Consumption
B.4.1 Detectors
In standby: 90 uA
In alarm: 6 mA
B.4.2 Modules
In standby: 120 uA
In alarm: 6mA
B.5 Notes on Loop wiring
Use suitably sized twisted shielded cable for the loop wiring. Connect the shield to earth using
terminal 3 or 6, connect it to one end of the loop only.
In order to allow the loop to function properly, you must section the device connection cable in such
way that any voltage drop along does not exceed 8 V. The following table shows the minimum
dimensions for the loop wiring with regard the distance between the Loop-O terminals and the most
distant device:
VDBS100 Deep Standard Base Deep Standard Base Allows connection to wall-mount cable runs
BLR100 Vega Relay Base Relay Base Relay activated by the detector R output attached
to the base
VBS100 Detector Sounder Base Base with Sounder Activated by the detector R output attached to the
base
Model Name Description Note
SGW2W Wire to Wireless
Translator
Connected to Loop, 32-device interface (Sagittarius
series - SG) wireless to panel
The panel sees the 32 devices as if they were
connected to the Loop (with different addresses)
SG100 Wireless Analogue
smoke detector
Wireless Analogue smoke
detector
Used only with SGW2W.
SG200 Wireless Analogue
Multicriteria detector
Wireless Optical/Heat
detector
SG350 Wireless Analogue
thermal detector
Wireless Analogue thermal
detector
(
a
)
a. Configured as “Rate-of-rise detector” at default (alarm is triggered by rapid rise in temperature or when the tempera-
ture exceeds the 54°C alarm threshold).
To configure as “High temperature detector” ( Rate-of-rise feature bypassed
and fixed temperature set at 70°C)
use the VPU100 programmer. The panel will recognize the configuration criteria
automatically.
SGMI100 Wireless Input Module Wireless Input Module
SGMC100 Wireless Output module Wireless Output module
SGCP100 Wireless Call Point Wireless Call Point
SGRS100 Wireless Sounder Wireless Sounder
up to 500 m
min. 1 mm
2
up to 1000 m
min. 1.5 mm
2
up to 1500 m
min. 2 mm
2
up to 2000 m
min 2.5 mm
2

Table of Contents

Other manuals for INIM Electronics SmartLoop

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics SmartLoop and is the answer not in the manual?

INIM Electronics SmartLoop Specifications

General IconGeneral
BrandINIM Electronics
ModelSmartLoop
CategoryControl Panel
LanguageEnglish

Related product manuals