66 Argus Devices
Installation and programming manual
B.4 Device Consumption
B.5 Configuring Argus devices
You can either use an Argus VPU100 programmer to set the Argus device addresses and then let
SmartLight enroll them or, launch the automatic addressing procedure provided by the SmartLight.
Note: Each loop supports up to 240 devices.
For detailed installation and addressing instructions, contact www.argussecurity.it.
B.5.1 Manual device addressing via VPU100
Addressing devices via VPU100
Work carefully through the Argus VPU100 addressing procedure and address all the devices.
Enrolling addresses
Once the Argus VPU100 addressing procedure has been completed, initialize the enrolling process.
From panel: <key>, Programming, Configuration, Loop, Ok, Auto configure, Acquire
B.5.2 Automatic setting of devices
The SmartLight can assign an address (1 to 240) automatically to each loop device, starting from the
device on the LOOP-0 (J18) terminal.
Note: The automatic addressing process will automatically delete the previous address.
Once all the loop device connections have been properly completed and double checked, initialize the
process.
From panel: <key>, Programming, Configuration, Loop, Ok, Auto configure, Readdress
Device in standby in alarm
Detectors 90 PA 6 mA
Modules 120 PA 6 mA