Chapter 5 Function Code Table
- 68 -
Function
Code
Parameter Name Function Description Setting Range Default
b7.12
Weighing check
weight 1
If the weighing function is enabled (b7.10 is set
to a non-zero value), perform weighing check as
follows:
1: In the empty car state, input the current load
weight into b7.12. The AC drive will store the load
weight and the corresponding analog data of the
weighing sensor (b7.14) in the empty state.
2. Put a load into the car and input the load weight
to b7.13 and complete the weighing check.
3. After you complete the preceding two steps, the
AC drive automatically generate the following "load
weight-analog voltage" curve.
Note: The load weight is calculated only when the
AC drive stops.
X-axis: load weight
Y-axis: weighing sensor analog voltage
Check
point 1
Check point 2
Check point
0.00
(x1)
X
2.00
(x2)
y
10000
(y1)
23000
(y2)
0.00 to 9.99
tons
0.00
tons
b7.13 Weighing check
weight 2
0.00 to 9.99
tons
0.00
tons
b7.14 Weighing check
analog voltage 1
0 to 32767 0
b7.15 Weighing check
analog voltage 2
0 to 32767 0
b7.16 Torque detection time
for overload limit
These two parameters are used to detect the output
torque in the overload limit function.
When the output frequency of the AC drive reaches
the setting of b7.17, the AC drive will keep output of
the frequency for the time set in b7.16.
In the constant-speed running state, the AC drive
detects the output torque for the overload limit
function (use of bE.13).
0.0 to 5.0s 0.5s
b7.17 Torque detection
frequency for overload
limit
Brake release
frequency
(b6.02)
to rated
frequency
(A0.04)
40.00 Hz
b7.18 Frequency limit When the CS200 is not connected to the elevator
controller and the input function 30# is inactive, the
running frequency is restricted by the value of this
parameter.
When the CS200 is connected to the elevator
controller, the elevator is the manual mode and the
input function 30# is inactive, the running frequency
is restricted by the value of this parameter.
Min. frequency
(b1.03) to
upward multi-
speed 1
(b5.00)
20.00 Hz