Chapter 5 Function Code Table                                                                                                                               
- 68 -
Function 
Code
Parameter Name Function Description Setting Range Default
b7.12
Weighing check 
weight 1
If the weighing function is enabled (b7.10 is set 
to a non-zero value), perform weighing check as 
follows: 
1: In the empty car state, input the current load 
weight into b7.12. The AC drive will store the load 
weight and the corresponding analog data of the 
weighing sensor (b7.14) in the empty state.
2. Put a load into the car and input the load weight 
to b7.13 and complete the weighing check.
3. After you complete the preceding two steps, the 
AC drive automatically generate the following "load 
weight-analog voltage" curve.
Note: The load weight is calculated only when the 
AC drive stops.
X-axis: load weight
Y-axis: weighing sensor analog voltage
Check 
point 1
Check point 2
Check point
0.00
(x1)
X
2.00
(x2)
y
10000
(y1)
23000
(y2)
0.00 to 9.99 
tons
0.00 
tons
b7.13 Weighing check 
weight 2
0.00 to 9.99 
tons
0.00 
tons
b7.14 Weighing check 
analog voltage 1
0 to 32767 0
b7.15 Weighing check 
analog voltage 2
0 to 32767 0
b7.16 Torque detection time 
for overload limit
These two parameters are used to detect the output 
torque in the overload limit function.
When the output frequency of the AC drive reaches 
the setting of b7.17, the AC drive will keep output of 
the frequency for the time set in b7.16.
In the constant-speed running state, the AC drive 
detects the output torque for the overload limit 
function (use of bE.13).
0.0 to 5.0s 0.5s
b7.17 Torque detection 
frequency for overload 
limit
Brake release 
frequency 
(b6.02) 
to rated 
frequency 
(A0.04)
40.00 Hz
b7.18 Frequency limit When the CS200 is not connected to the elevator 
controller and the input function 30# is inactive, the 
running frequency is restricted by the value of this 
parameter.
When the CS200 is connected to the elevator 
controller, the elevator is the manual mode and the 
input function 30# is inactive, the running frequency 
is restricted by the value of this parameter.
Min. frequency 
(b1.03) to 
upward multi-
speed 1 
(b5.00)
20.00 Hz