Function
Code
Parameter Name Setting Range Min. Unit Default Property
frequency
F4-15
I1 maximum input F4-13 to 10.00 V 0.01 V 10.00 V ƿ
F4-16
I1 maximum input
frequency
-100.00%–100.0% 0.1% 100.0% ƿ
F4-17
I1 filter time
0.00–10.00s 0.01s 0.10s ƿ
F4-18
I2 minimum input
0.00 V to F4-20 0.01 V 0.00 V
F4-19
I2 minimum input
frequency
-100.00%–100.0% 0.1% 0.0% ƿ
F4-20
I2 maximum input 0.00–10.00 V 0.01 V 10.00 V ƿ
F4-21
I2 maximum input
frequency
-100.00%–100.0% 0.1% 100.0% ƿ
F4-22
I2 filter time
0.00–10.00s 0.01s 0.10s ƿ
F4-23
I3 minimum input
0.00 V to F4-25 0.01V 0.00V ƿ
F4-24
I3 minimum input
frequency
-100.00%–100.0% 0.1% 0.0% ƿ
F4-25
I3 maximum input 0.00–10.00 V 0.01 V 10.00 V ƿ
F4-26
I3 maximum input
frequency
-100.00%–100.0% 0.1% 100.0% ƿ
F4-27
I3 filter time
0.00–10.00s 0.01s 0.10s ƿ
Group F5: Output terminals
F5-00
FM terminal output
mode selection
0: Pulse output (FMP)
1: Open-collector output (FMR)
1 0 ƿ
F5-01
FMR function
selection
(open-collector
output terminal)
1 0 ƾ
F5-02
Control board relay1
output selection
(T/A-T/B-T/C)
1 21 ƿ
F5-03
Extension card
relay2 output
selection
(P/A-P/B-P/C)
1 0 ƿ
F5-04
DO1 function
selection
(open-collector
output terminal)
1 2 ƿ
F5-05
Extension card DO2
function selection
0: No output
1: AC drive running
2: Fault output (stop)
3: Frequency-level detection (FDT)
output
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Motor 1 connection indication
9: Motor 2 connection indication
10: Motor 3 connection indication
20: Communication setting
21: Brake output
22: Low-speed shaft brake output
Other: Reserved
1 0 ƿ
F5-06
FMP function
selection (pulse
output terminal)
0 ƿ
F5-07
O1 function
selection (AO1)
0 ƿ
F5-08
O2 function
selection (AO2)
0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
7: AI1
8: AI2
9: AI3 (provided by I/O extension
card)
Other: Reserved
1
1 ƿ
F5-09
Maximum FMP
output frequency
0.01–100.00 kHz 0 kHz 50.0 kHz ƿ