Function
Code
Parameter Name Setting Range Min. Unit Default Property
F8-08
Low-voltage
protection threshold
380.0–500.0 V 0.1 V 400.0 V ƾƾ
F8-09
Low-speed hoisting
torque limit
0.0%–150.0% 0.1% 0.0% ƾ
F8-10
Torque detection
frequency
0.00–50.00 Hz 0.01 Hz 40.00 Hz ƾ
F8-11
Torque detection
time
0.0–5.0s 0.1s 0.5s ƾ
F8-12
Forward/Reverse
rotation dead-zone
time
0.0–3000.0s 0.1s 0.5s ƿ
F8-14
Relay card
enable/K2 function
selection
0–122 1 0 ƿ
F8-16
Over-modulation
enable
0: Over-modulation invalid
1: Over-modulation valid
1 1 ƿ
F8-17
A
ccumulative
running time setting
0–65000 h
1 h 65535 h ƿ
F8-19
Frequency detection
value (FDT level)
0.00 Hz to maximum frequency 0.01 Hz 50.00 Hz ƿ
F8-20
Frequency detection
hysteresis value
(FDT hysteresis)
0.0%–100.0% (FDT level) 0.1% 5.0% ƿ
F8-22
Protection detection
of short circuit to
ground at power on
0: Invalid
1: Valid
1 1 ƿ
F8-23
A
ction selection at
running time reached
0: Continue to run
1: Stop
1 0 ƾ
Group F9: Faults and protection
F9-00
Motor overload
protection selection
0: Disabling motor overload
protective function
1: Enabling motor overload
protective function
1 1 ƿ
F9-01
Motor overload
protection gain
0.20–10.00 0.01 1.00 ƿ
F9-02
Motor overload
pre-warning
coefficient
50%–100% 1% 80% ƿ
F9-03
Over-voltage stall
gain
0 (no stall overvoltage) to 100
1 0 ƿ
F9-04
Over-voltage stall
protection voltage
120%–150%
1% 130% ƿ
F9-05
Over-current stall
gain
0–100 1 20 ƿ
F9-06
Over-current stall
protection current
100%–200%
1% 150% ƿ
F9-12
Input phase loss
protection
0: Disabled
1: Enabled
1 1 ƿ
F9-13
Output phase loss
protection
0: Disabled
1: Enabled
1 1 ƿ
F9-14 1st fault type Err02: Over-current during / / Ɣ
efesotomas
y
on.com