Electrical Installation
‑117‑
T3
Figure 7‑10 Main circuit terminal dimensions of T3 models
Table 7–5 Recommended main circuit cables for T3 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T3
MD500T7.5GB‑PLUS 21.9 3 x 4 TNR3.5‑5 4 TNR3.5‑5 M5
2.8 (24.8)
MD500T11GB‑PLUS 32.2 3 x 6 TNR5.5‑5 6 TNR5.5‑5 M5
2.8 (24.8)
T4
Figure 7‑11 Main circuit terminal dimensions of T4 models
Table 7–6 Recommended main circuit cables for T4 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T4 MD500T15GB‑PLUS 41.3 3 x 10 TNR8‑5 10 TNR8‑5 M5
2.8 (24.8)