EasyManua.ls Logo

Inovance MD500-PLUS Series - Page 118

Inovance MD500-PLUS Series
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation
‑117‑
T3
Figure 7‑10 Main circuit terminal dimensions of T3 models
Table 7–5 Recommended main circuit cables for T3 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T3
MD500T7.5GB‑PLUS 21.9 3 x 4 TNR3.5‑5 4 TNR3.5‑5 M5
2.8 (24.8)
MD500T11GB‑PLUS 32.2 3 x 6 TNR5.5‑5 6 TNR5.5‑5 M5
2.8 (24.8)
T4
Figure 7‑11 Main circuit terminal dimensions of T4 models
Table 7–6 Recommended main circuit cables for T4 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T4 MD500T15GB‑PLUS 41.3 3 x 10 TNR8‑5 10 TNR8‑5 M5
2.8 (24.8)