Electrical Installation
118
T5
Figure 7‑12 Main circuit terminal dimensions of T5 models
Table 7–7 Recommended main circuit cable selection for T5 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T5
MD500T18.5G(B)‑
PLUS
MD500T18.5G(B)‑T‑
PLUS
49.5 3 x 10 GTNR10‑6 10 GTNR10‑6 M6
4.8 (45.2)
MD500T22G(B)‑
PLUS
MD500T22G(B)‑T‑
PLUS
59.0 3 x 16 GTNR16‑6 16 GTNR16‑6 M6
4.8 (45.2)
T6
Figure 7‑13 Main circuit terminal dimensions of T6 models