Advisor Advanced ATSx000A(-IP) Installation and Programming Manual 237
Options affected by EN 50131 regulations
EN 50131 Grade 2
Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
• 1.2.6.n.2 Period / Time, 24 h for every path to meet ATS Class 2, 4 h for the
IP path to meet ATS Class 4.
• 2.2.1.n.3.3 View areas and 2.2.1.n.3.4 Control areas settings are identical
• 2.2.1.n.3.8 Buzzer silent, never
• 2.2.1.n.3.9 Quick set, off
• 2.2.1.n.3.10 Function keys, all set to None
• 2.2.1.n.3.15 ACK on keypad, set to None for non-LCD keypads
• 3.1.n.7.3 SMS control, disabled for all users
• 3.2.n.5 User group options, 25. No OP/CL reports option set to No
• 4.1.n.6.1 Inhibit, set to No for all zones with type 5. Panic, 6. 24H
• 4.1.n.6.5 Swinger shunt, set to Yes for all zones
• 4.1.n.6.25 ACK on keypad, set to None for all zones with type 9. Keyswitch
• 5.n.3 Entry time, 45 s maximum
• 5.n.7 Entry alarms, Instant
• 7.5.n.2 Active, set to No for all schedules.
• 8.1.2.1 Activation, external siren 90 to 900 s
• 8.1.2.2 Delay time, external siren 600 s maximum
• 8.1.3.1 Armed display, 30 s maximum
• 8.1.3.4 Mains reporting delay, 3600 s maximum
• 8.2.1 User code required, enabled
• 8.3.1 Armed display, always
• 8.3.3 Alarm list, disabled
• 8.4.1 RTS options, all enabled except zone technical alarm, which is optional
• 8.4.2 Inhibit includes, all allowed except engineer reset, which must be
disabled
• 8.4.5 Pending alarms, enabled
• 8.5.4 Swinger shunt ≥ 3
• 8.5.5 Report restore, on ACK
• 9.3.n.2 Line fault, enabled per path used
• 9.3.n.3 Line fault delay, 0 s
It is required to apply the following supervision settings for wireless DGPs:
• Short supervision: 20 minutes
• Long supervision: 2 hours
• Smoke supervision: 4 hours
Refer to appropriate sections and manuals.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Interlogix Advisor Advanced ATS 000A Series and is the answer not in the manual?

Interlogix Advisor Advanced ATS 000A Series Specifications

General IconGeneral
BrandInterlogix
ModelAdvisor Advanced ATS 000A Series
CategoryControl Panel
LanguageEnglish

Related product manuals