Chapter 1: Installation
CDC4 Door Controller Installation and Programming Manual 37
Standalone current draw
The current draw of the standalone board running from battery power is shown in
Specificationson page 41 for various scenarios, assuming the board is
operating normally with the following attributes:
Battery charging is off
Siren is not active
There is no additional current load connected
The eight inputs are in normal state and use 4.7 kΩ EOL resistors
The four onboard outputs are not active
There is no output expander attached
USB is not connected
The system data bus is terminated and is connected to an Advisor Advanced
panel
The local buses (bus 1 and bus 2) are not terminated and not active
Note: Relay coil current forms part of the allowable user current draw. Refer to
Output fusing and user current drawon page 38.