Chapter 1: Installation
CDC4 Door Controller Installation and Programming Manual 41
Specifications
Mains power specifications
Mains input voltage
230 VAC +10%, −15%, 50 Hz 10%
Transformer output
19 VAC, SELV Class I power limited
Power supply specifications
Power supply voltage
13.8 V 0.2 V
Main board consumption
226 mA (whilst battery voltage is 12.0 V)
Note: Active Ethernet adds 25 mA. Each active relay
coil adds 55 mA.
See also “Output fusing and user current drawon page
38.
Auxiliary power output (AUX. POWER)
13.8 V 0.2 V, 1 A max.
Door lock relay switching capacity:
Maximum (resistive/load)
Minimum
3 A, 30 V DC
100 mA, 5 V DC
Battery power output (BAT)
13.8 V 0.2 V, 2.5 A max.
Battery type
Lead acid rechargeable:
12 Ah, 12 V nom. (BS130N)
18 Ah, 12 V nom. (BS131N)
26 Ah, 12 V nom. (BS129N)
Ethernet connection
Supported standard
IEEE 802.3u
Speed
10BASE-T or 100BASE-TX
Duplex
Half-duplex and full-duplex
Cabling
FTP (foiled twisted pair) Cat 5e cable or better
Autonegotiation
MDIX
Environmental
Storage temperature
20 to +80°C
Operating temperature
0 to +50°C
Maximum relative humidity
93% noncondensing
IP protection grade
IP31
Colour
Beige
Dimensions (W x H x D)
409 x 593 x 112 mm
Weight
10.22 kg
Fuses
Mains, mains fuse
M205 (5x20 mm) 1 A 250 VAC slow blow
Battery
3AG/3AB (6x32 mm) 8 A 250 VAC slow blow