Goodrive300-19 series open loop vector inverter special for hosit Fault tracking
-192-
supply is too low;
The setting of motor rated
current is incorrect;
The motor stall or load
transients is too strong
supply line;
Reset the rated current of the
motor
Check the load and adjust the
torque lift
The acceleration is too fast;
Reset the rotating motor;
The voltage of the power
supply is too low;
The load is too heavy;
The motor power is too
small
Increase the ACC time;
Avoid the restarting after
stopping;
Check the power of the
supply line;
Select an inverter with bigger
power;
Select a proper motor
Phase loss or fluctuation of
input R,S,T
Check input power;
Check installation distribution
U, V, W phase loss output
(or three phases of the load
are seriously asymmetrical)
Check the output distribution;
Check the motor and cable
Rectifying module
overheat
Air duct jam or fan damage;
Ambient temperature is too
high;
The time of overload
running is too long
Dredge the air duct or change
the fan;
Low the ambient temperature
SI external fault input
terminals action
Check the external device
input
The baud rate setting is
incorrect;
Fault occurs to the
communication wiring;
The communication
address is wrong;
There is strong interference
to the communication
Set proper baud rate;
Check the communication
connection distribution;
Set proper communication
address;
Change or replace the
connection distribution or
improve the anti-interference
capability
The connection of the
control board is not good;
Hoare component is
Check the connector and
repatch;
Change the Hoare;