Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-147-
6: Coast to stop
7: Fault reset
8: Operation pause
21: ACC/DEC time 1
22: ACC/DEC time 2
30: ACC/DEC disabling
P08.06
Jogging
frequency
0.00Hz ~P00.03 (the Max. frequency)
5.00Hz
P08.07
Jogging ACC
time
0.0~3600.0s
Depend
on model
P08.08
Jogging DEC
time
0.0~3600.0s
Depend
on model
P08.00
ACC time 2
0.0~3600.0s
Depend
on model
P08.01
DEC time 2
0.0~3600.0s
Depend
on model
P08.02
ACC time 3
0.0~3600.0s
Depend
on model
P08.03
DEC time 3
0.0~3600.0s
Depend
on model
P08.04
ACC time 4
0.0~3600.0s
Depend
on model
P08.05
DEC time 4
0.0~3600.0s
Depend
on model
P08.28
Fault reset
times
0~10
0
P08.29
Interval time
of automatic
fault reset
0.1~3600.0s
1.0s
7.8 Frequency setting
Goodrive300-19 series inverters can set the frequency by various means. The reference channel can
be divided into main reference channel and assistant reference channel.
There are two main reference channels: A frequency reference channel and B frequency reference