Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-146-
FWD/REV
rotation
2: Switch after the speed reaches P01.15 and delays for
P01.24
P01.15
Stopping
speed
0.00~100.00Hz
0.50Hz
P01.16
Detection of
stopping
speed
0: Detect according to speed setting (no stopping delay)
1: Detect according to speed feedback (only valid for
vector control)
1
P01.18
Terminal
running
protection
when
powering on
0: The terminal running command is invalid when powering
on.
1: The terminal running command is valid when powering
on.
0
P01.19
Action if
running
frequency<
lower limit
frequency
(valid>0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
P01.20
Hibernation
restore delay
time
0.0~3600.0s (valid when P01.19=2)
0.0s
P01.21
Restart after
power off
0: Disable
1: Enable
0
P01.22
The waiting
time of restart
after power
off
0.0~3600.0s (valid when P01.21=1)
1.0s
P01.23
Start delay
time
0.0~60.0s
0.0s
P01.24
Delay time of
stop speed
0.0~100.0s
0.0s
P05.01~
P05.09
Multi-function
digital input
terminal
1: Forward rotation operation
2: Reverse rotation operation
4: Forward jogging
5: Reverse jogging