Goodrive300-19 series open loop vector inverter special for hosit Fault tracking
-194-
Parameters
uploading fault
The connection of the
keypad wires is not good or
broken;
The keypad wire is too long
and affected by strong
interference;
Communication fault
Check the environment and
eliminate interference source;
Change the hardware and
ask for service;
Change the hardware and
ask for service;
Parameters
downloading fault
The connection of the
keypad wires is not good or
broken;
The keypad wire is too long
and affected by strong
interference;
There is mistake on the
data storage of the keypad
Check the environment and
eliminate interference source;
Change the hardware and
ask for service;
Repack up the data in the
keypad
Grounding shortcut
fault 1
The output of the inverter is
short circuited with the
ground;
There is fault in the current
detection circuit
The actual motor power
sharply differs from the
inverter power.
Check if the connection of the
motor is normal or not;
Change the hoare;
Change the main control
board
Set motor parameters
correctly
Grounding shortcut
fault 2
The output of the inverter is
short circuited with the
ground;
There is fault in the current
detection circuit
The actual motor power
sharply differs from the
inverter power.
Check if the connection of the
motor is normal or not;
Change the Hoare;
Change the main control
board
Set motor parameters
correctly
The load is too heavy or
stalled
Check the load and ensure it
is normal. Increase the
detection time;
Check whether the control
parameters are normal
The autoturn parameter is
Check whether the control