EasyManua.ls Logo

Johnson Controls Frick RWB II - PID Setup

Johnson Controls Frick RWB II
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RWB II ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.200-IOM (DEC 11)
Page 23
Integral control will increase the output in increments,
over time, to correct the control input to the setpoint.
Control Input Output %
150°F 0%
155°F 20%
160°F 40%
165°F 60%
170°F 80%
175°F 100%
Figure 21 - Analog Output Calibration
Figure 22 - PID Setup
Based on these descriptions set PID #1 for EZ‑Cool
LIOC
per Figure 22 as a starting point. Tuning of the output will be
required. There should be no need to use a derivative gain.
SUCTION CHECK VALVE
Low temperature booster compressor operations require
a more positive suction check valve closure. This is ac
complished by allowing the high stage discharge pressure
gas to assist the spring tension and intermediate pressure
closing force.

Table of Contents

Related product manuals