Hardware Installation—Installing the IFC-1010/2020
125
This unit must be installed in accordance with the following requirements:
•
Monitor modules located within the protected premises that are
responsible for supervising the state of the protected premises control
unit may be programmed for Tracking (non-latching) operation.
Notification appliances and control relays will follow the tracking
devices programmed to activate them. Once a tracking device input
circuit is restored to normal, the fire alarm condition clears from that
device, all output devices assigned to the tracking device will return to
their non-fire alarm state. This action will occur without activation of
the system reset button.
•
The display terminal and printer must be located in the same room as
the IFC-1010/2020.
•
The display terminal and printer must be powered by an
uninterruptable power supply UL Listed for Fire Protective Signaling.
This power source must be supervised by the control panel.
•
The keyboard connected to the display terminal must not be removed
or made inaccessible at any time.
•
Loop interface board requirement:
LIB-200: 10,000 feet (3048 m) at 12 AWG (3.25 mm
2
) maximum
distance between the Central/Receiving Unit and the
NIB-96 or M50xMJs.
LIB-200A:12,500 feet (3810 m) at 12 AWG (3.25 mm
2
) maximum
distance between the Central/Receiving Unit and the
NIB-96 or M50xMJs.
LIB-400: 12,500 feet (3810 m) at 12 AWG (3.25 mm
2
) maximum
distance between the Central/Receiving Unit and the
NIB-96 or M50xMJs.
Notes:
1.
The use of a DACT (NFPA 72 Supervising Station Fire Alarm
Systems) is not permitted when one or more of the following are
present in the system: SIB-NET, XP Transponder with separate power
supply, APS-6R, AA-120/E, AA-100/E, AA-30/E or a second
(remote) MPS-24A or MPS-24AE power supply.
2. All LIBs are power-limited. If the wiring connected to the LIB-200
leaves the building, it must be in conduit. It cannot exceed
1000 meters (1093 yards), must not cross any power lines, and
must not be in the vicinity of any high voltage. These outdoor wiring
restrictions do not apply to the LIB-200A or the LIB-400. Refer to the
Loop Interface Boards (LIB-200, LIB-200 A, and LIB-400) section in
this document.