Motor Current Limit
Access Level Required: OPERATOR
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the motor
current reaches this value, the pre-rotation vanes will
not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close
to reduce the current to this value.
Pulldown Demand Limit
Access Level Required: OPERATOR
Allows the user to specify the current limit value (as
a percentage of Full Load Amps) to which the chiller
will be limited during the specied pulldown limit time.
This value will override the Motor Current Limit value
during this time period. This function is used to provide
energy savings following chiller start-up.
Pulldown Demand Time
Access Level Required: OPERATOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chiller
starts.
Print
Access Level Required: VIEW
Generates Setpoints print report.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Setup
Access Level Required: VIEW
Moves to the sub-screen allowing setup of general
system parameters.
Quick Start
(Software version C.OPT.01.21.307 and later)
Access Level Required:
ADMIN (to initially enable the feature);
SERVICE (if feature is enabled)
Moves to the sub-screen allowing the Quick Start feature
to be enabled/disabled. Once enabled, this screen allows
programming and viewing of Quick Start setpoints and
parameters.