JOHNSON CONTROLS
64
FORM 160.54-O1
OptiView Control Center
Variable Speed Oil Pump Speed Control:
Set
Access Level Required: SERVICE
This key allows the user to specify a xed manual speed
at which the VSOP will run.
Raise
Access Level Required: SERVICE
This key puts the VSOP control into Manual Mode and
increments the present Speed Command by 0.5 Hz.
Lower
Access Level Required: SERVICE
This key puts the VSOP control into Manual Mode and
decrements the present Speed Command by 0.5 Hz.
Auto
Access Level Required: SERVICE
This key returns the VSOP to Automatic Mode where
control is based on the Oil Pressure setpoint.
Manual Pump
Access Level Required: OPERATOR
This key puts the Oil Pump control in Manual Mode and
forces it to RUN. The Oil Pump is limited to running for
a maximum of ten (10) minutes. If a longer running time
is desired, this key must be pressed again. Manual Oil
Pump control is disabled (and the button hidden) during
system prelube, system run, proximity probe calibration,
seal lubrication, and system coastdown.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.