EasyManuals Logo

Jung Smart Control SC 1000 KNX User Manual

Jung Smart Control SC 1000 KNX
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #202 background imageLoading...
Page #202 background image
Art. No. SC 1000 KNX
In addition, the setpoint can be transmitted cyclically. The "Cyclical transmission of setpoint
temperature" parameter determines the cycle time (1 to 255 minutes). The value "0" will
deactivate the periodical transmission of the setpoint temperature value. It has to be pointed out
that with deactivated periodical transmission and deactivated automatic transmission, no
setpoint temperature telegrams will be transmitted in case of a change.
Setting the "Read" flag on the "Setpoint temperature" object makes it possible to read out the
current setpoint. Following the return of bus voltage or after re-programming via the ETS, the
object value will be initialised according to the current setpoint temperature value and actively
transmitted to the bus.
Page 202 of 347
Software "Smart Control 501511"
Functional description

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals