Art. No. SC 1000 KNX
Bit of the status telegram Meaning
0 On "1": Comfort operation activated
1 On "1": Standby mode active
2 On "1": Night mode active
3 On "1": Frost/heat protection mode active
4 On "1": Controller disabled
5 On "1": Heating, on "0": Cooling
6 On "1": Controller inactive (deadband)
7 On "1": Frost alarm (T
Room
≤ +5 °C)
Bit encoding of the 1 byte status telegram
Bit of the
status telegram
Meaning on "1" Meaning on "0"
0 Normal operating mode Forced operating mode
1 Comfort extension active No comfort extension
2 Presence (Motion detector) No presence
(Motion detector)
3 Presence (Presence button) No presence
(Presence button)
4 Window opened No window opened
5 Additional level active Additional level inactive
6 Heat protection active Heat protection inactive
7 Controller disabled
(dew point operation)
Controller not disabled
Bit encoding of the 1 byte additional status telegram