Art. No. SC 1000 KNX
Split unit (4 K / 90 min)
via control parameter
setting, it is possible to set the control
parameters in a manner deviating from
the predefined values within specific
limits.
This parameter is only visible if "Type of
cooling control = PI control".
Proportional range
cooling
(10...127) * 0.1 K
10...50...127 Separate setting of the "Proportional
range" control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Reset time cooling
(0...255) * 1 min; 0 =
inactive
0...150...255 Separate setting of the "Reset time"
control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Top hysteresis of the
2-point controller
cooling
(5...127) * 0.1 K
5...127 Definition of top hysteresis (switch-on
temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Cooling
2-point controller
hysteresis lower limit
(-128...–5) * 0.1 K
-128...-5 Definition of bottom hysteresis (switch-
off temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Operating mode switch-
over
Via value (1 byte)
Via switching (4 x 1 bit)
In the setting "Via value (1-byte) the
change-over of the operating modes via
the bus takes place according to the
KNX specification via a 1-byte value
object. In addition, a higher-ranking
forced-object is available for this setting.
In the setting "Via switching (4 x 1 bit)
" the ‘classic’ change-over of the
operating modes via the bus is via four
separate 1-bit objects.
Operation mode after
reset
Restore operation mode
before reset
Comfort mode
Standby mode
Night operation
Frost/heat protection mode
This parameter specifies which
operating mode is set immediately after
a device reset.
With "Restore operation mode before
reset": The mode set before a reset
according to the operating mode object
or by push button function (normal
priority) will be restored after the
initializing phase of the device.
Operating modes set by a function with
a higher priority before the reset
(Forced, Window status, Presence
Page 287 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals