actual fan levels. The fan controller
automatically corrects a faulty
parameterisation by activating level 1 for
the start-up, meaning that the fan starts
up normally without a switch-on level.
Command value is 0%,
until internal command
value is greater than,
*1%
1...100 The command value evaluated by the
fan controller in automatic operation can
be optionally limited by this parameter in
the bottom command value range.
Command value is
100%, as soon as
internal command value
is greater than,
*1%
1...99...100 The command value evaluated by the
fan controller in Automatic mode can be
optionally limited by this parameter in
the top command value range.
Command value offset,
*1%
0...100 The command value evaluated by the
fan controller in Automatic mode can be
optionally raised by the static offset
configured here. Should the calculation
produce a value of over 100 %, then the
command value is limited to the
maximum value.
h Room temperature control (RTC) -> Controller general -> Command value and status output
Automatic transmission
at modification by
(0...100) * 1 %;
0 = inactive
0...3...100 This parameter determines the size of
the command value change that will
automatically transmit continuous
command value telegrams via the
command value objects. Thus this
parameter only affects command values
which are configured to "Continuous PI
control" and to the 1 byte additional
command value objects of the
"Switching PI control (PWM)".
Cycle time of the
switching command
value
(1...255) * 1 min
1...15...255 This parameter specifies the cycle time
for the pulse width modulated command
value (PWM). Thus this parameter only
affects command values which are
configured to "Switching PI control
(PWM)".
Cycle time for automatic
transmission
(0...255) * 1 min;
0 = inactive
0...10...255 This parameter determines the time
interval for the cyclical transmission of
the command values via all command
value objects.
Output of the heating
command value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for heating is output normally or in
inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured and not two-
level operation.