Art. No. SC 1000 KNX
command value. The controller
transmits a 0 % command value if no
more heating or cooling energy has to
be demanded.
Maximum command
value for cooling
(optionally also for basic
and additional level)
55%, 60%, 65%, 70%,
75%, 80%, 85%, 90%,
95%, 100%
The "Maximum command value"
parameter specifies the upper command
value limiting value for cooling. With an
active command value limit, the set
maximum command value is not
exceeded. If the controller calculates
larger command values, it sets the
configured maximum command value.
Heating message Yes
No
Depending on the set operating mode, a
separate object can be used to signal
whether the controller for the first control
circuit is currently demanding heating
energy and is thus actively heating. The
"Yes" setting here enables the message
function for heating.
Cooling message Yes
No
Depending on the set operating mode, a
separate object can be used to signal
whether the controller for the first control
circuit is currently demanding cooling
energy and is thus actively cooling. The
"Yes" setting here enables the message
function for cooling.
Controller status no status
KNX compliant
Controller general
Transmit individual state
The room temperature controller can
transmit its current status to the KNX/
EIB. A choice of data formats is
available for this. This parameter
enables the status signal and sets the
status format.
Single status Comfort mode
Active Standby mode
activated
Night mode activated
Frost/heat protection active
Controller disabled
Heating / cooling
Controller inactive
Frost alarm
Here, the status information is defined,
which is to be transmitted onto the bus
as the 1-bit controller status.
This parameter is only visible if the
parameter "Controller status" is set to
"Transmit single status".
Page 295 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals