Art. No. SC 1000 KNX
derived directly from the basic setpoint
resulting from the half deadband (Basic
setpoint - 1/2 deadband = Heating
comfort temperature or Basic setpoint +
1/2 deadband = Cooling comfort
temperature).
Asymmetrical setting: with this setting
the comfort setpoint temperature for
heating equals the basic setpoint! The
preset deadband is effective only from
the basic setpoint in the direction of
comfort temperature for cooling. Thus
the comfort set-temperature for cooling
is derived directly from the comfort
setpoint for heating.
The parameter is only visible in "Heating
and cooling" operating modes (if
necessary with additional levels)!
Deadband between
heating and cooling
(0...127) * 0.1 K
0...20...127 The comfort setpoint temperatures for
heating and cooling are derived from the
basic setpoint in consideration of the
adjusted deadband. The deadband
(temperature zone for which there is
neither heating nor cooling) is the
difference between the comfort setpoint
temperatures. It is set using this
parameter.
The parameter is only visible in "Heating
and cooling" operating modes (if
necessary with additional levels).
Difference between
basic and additional
levels
(0...127) * 0.1 K
0...20...127 In a two-level control mode, it is
necessary to determine the temperature
difference to the basic level with which
the additional level is to be incorporated
into the feedback control. This
parameter defines the level spacing.
The parameter can only be seen in two-
level control operation.
Transmission at
setpoint temperature
change by
(0...255) * 0.1 K
0...1...255 Determines the size of the value change
required to automatically transmit the
current value via the "Setpoint
temperature" object. In the "0" setting,
the setpoint temperature is not
transmitted automatically when there is
a change.
Cyclical transmission of
setpoint temperature
(0...255) * 1 min;
0 = inactive
0...255 This parameter determines whether the
setpoint temperature is to be transmitted
periodically via the "Setpoint
temperature" object. Definition of the
Page 299 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals